Abstract Distribution-network reconfiguration changes the equivalent feeder impedance seen from a soft open point (SOP), thereby invalidating fixed-parameter analytical voltage-control models. This paper proposes a residual-triggered active sensitivity estimation method for model-assisted power optimization using an SOP (MAPO-SOP). An analytical point of common coupling (PCC) voltage model is first formulated to coordinate active and reactive power under the converter apparent-power constraint.